Selection of Generating Sets according to Given Output Continuous Duty Range (KVA):  Click here   Italiano   English
The Company
Presentation
Where
The products
Generating Sets
Control Boards
Cabs/Canopies
Containers
Fuel Tanks
The Services
Our Services
Contact us
Our Addresses
 

SIGEM GENERATING SETS, ASSEMBLED WITH
WATER COOLED DIESEL ENGINE
1500 RPM   400 V   50 Hz

(1) Output in continuous duty with variable load, with no time limit running, and with average load permitted not more than 75%. Overload of 10% is permitted, in intermittent duty, for 1hour each 12 hours of operation. (PRIME POWER)(PRP).

(2) Output in stand-by duty with a variable load and with average load permitted not more than 85%. No overload is permited. Running in case of public mains failure with a maximum time limit of 300 hours per year. (LIMITED-TIME RUNNING POWER ) ( LTP). Powers refer to ISO 8528-1 specification (power factor 0.8) and to the following site conditions  (as to ISO 3046 specification) Barometrical pressure 100 kPA - Temperature 25° C - Relative Humidity 30%.
(3) Diesel engine four-stroke, direct injection.
(4) L = Vertical in line configuration, V = "V" configuration
(5) NA = Naturally aspirated, TA = Turbocharged, TCA = Turbocharged and aftercooled
(6) Governor: M = Mechanical - E = Electronic
(7) Dimensions referred to regular immovable base types; for special ones equipped with accessories, dimensions and weight will increase or decrease.

All data subject to change without notice.
 
Generating set  SIGEM
type
Output
continuous duty
KVA  (1)  KW
Output
stand-by duty
kVA (2)  KW
Diesel engine type
(3)
Number of cylinders
(4)
Total displacement
liters
Air induction system
(5)
Governor
(6)
Generating set overall dimensions
length x width x height
mm  (7)
Weight
kg
 
C 50.5 50  40 58   46 4BT3.9G3 4 L 3,9 TC M 1800x850x1300

1200

C 60.5 60  48 68   54 4BT3.9G4 4 L 3,9 TC M 1800x850x1300

1500

C 85.5 85  68 93   74 6BT5.9G5 6 L 5,9 TC M 2300x900x1350

1650

 
C 105.5 105  84 115   92 6BT5.9G6 6 L 5,9 TC M 2300x900x1350

1850

 
C 130.5 130  104 145   116 6CT8.3G2 6 L 8,3 TC M 2300x900x1400

2100

 
C 180.5 180  144 200   160 6CTA8.3G2 6 L 8,3 TCA M 2300x900x1400

2200

 
C 200.5 200  160 220   176 6CTAA8.3G1 6 L 8,3 TCA E 2300x900x1400

2300

 
C 250.5 250  200 275   220 M11-G2 6 L 10,8 TCA E 2600x1000x1600

2400

 
C 315.5 315  252 350   280 NT855G6 6 L 14 TC E 2600x1000x1800

2800

 
C 360.5 360  288 400   320 NTA855G4 6 L 14 TCA E 2600x1000x1800

2900

 
C 400.5 400  320 450   360 QSX15G4 6 L 15 TCA E 3200x1400x1850

3400

 
C 460.5 460  368 515   412 QSX15G6 6 L 15 TCA E 3200x1400x1850

3600

 
C 500.5 500  400 560   448 QSX15G8 6 L 15 TCA E 3200x1400x1850

3800

 
C 640.5 640  512 705   564 VTA28G5 12 V 28 TCA E 3800x1450x2300

5200

 
C 930.5 930  744 1030   824 KTA38G3 12 V 37,7 TCA E 4200x1750x2400

7500

 
C 1030.5 1030  824 1130   904 KTA38G5 12 V 37,7 TCA E 4200x1750x2400

7800

 
C 1290.5 1290  1032 1425   1140 KTA50G3 16 V 50,3 TCA E 5300x1800x2450

9100

 
C 1400.5 1400  1120 1625   1300 KTA50G8 16 V 50,3 TCA E 5400x2000x2500

9800

 
 
MTU
CUMMINS
MAN
VOLVO PENTA
IVECO Motors
SAME Diesel
PERKINS
MANUAL
SWITCH BOARDS
AUTOMATIC AT30

AUTOMATIC AT100

BURIED TANKS
EXTERNAL TANKS
      8 ÷     30
    31 ÷     60
    61 ÷   100
  101 ÷   190
  191 ÷   300
  301 ÷   400
  401 ÷   600
  601 ÷   900
  901 ÷ 1750