Selection of Generating Sets according to Given Output Continuous Duty Range (KVA):  Click here   Italiano   English
The Company
Presentation
Where
The products
Generating Sets
Control Boards
Cabs/Canopies
Containers
Fuel Tanks
The Services
Our Services
Contact us
Our Addresses
 

SIGEM GENERATING SETS, ASSEMBLED WITH
WATER COOLED DIESEL ENGINE
1500 RPM   400 V   50 Hz

(1) Output in continuous duty with variable load, with no time limit running, and with average load permitted not more than 75%. Overload of 10% is permitted, in intermittent duty, for 1hour each 12 hours of operation. (PRIME POWER)(PRP).

(2) Output in stand-by duty with a variable load and with average load permitted not more than 85%. No overload is permited. Running in case of public mains failure with a maximum time limit of 300 hours per year. (LIMITED-TIME RUNNING POWER ) ( LTP). Powers refer to ISO 8528-1 specification (power factor 0.8) and to the following site conditions  (as to ISO 3046 specification) Barometrical pressure 100 kPA - Temperature 25° C - Relative Humidity 30%.
(3) Diesel engine four-stroke, direct injection.
(4) L = Vertical in line configuration, V = "V" configuration
(5) NA = Naturally aspirated, TA = Turbocharged, TCA = Turbocharged and aftercooled
(6) Governor: M = Mechanical - E = Electronic
(7) Dimensions referred to regular immovable base types; for special ones equipped with accessories, dimensions and weight will increase or decrease.

All data subject to change without notice.
 
Generating set  SIGEM
type
Output
continuous duty
KVA  (1)  KW
Output
stand-by duty
kVA (2)  KW
Diesel engine type
(3)
Number of cylinders
(4)
Total displacement
liters
Air induction system
(5)
Governor
(6)
Generating set overall dimensions
length x width x height
mm  (7)
Weight
kg
 
M  210.5 210   168 240   192 D2866TE20 6 L 11,97 TC M 2900x1000x1650

2200

M  260.5 260   208 290   232 D2866LE211 6 L 11,97 TCA E 2950x1100x1700

2650

M  310.5 310   248 350   280 D2866LE201 6 L 11,97 TCA E 2950x1100x1700

2900

 
M  415.5 415   332 460   368 D2848LE201 8 V 14,62 TCA E 3000x1400x1950

3800

 
M  510.5 510   408 570   456 D2840LE201 10 V 18,27 TCA E 3200x1450x2000

4300

 
M  630.5 630   504 700   560 D2842LE201 12 V 21,93 TCA E 3600x1500x2100

5500

 
 
MTU
CUMMINS
MAN
VOLVO PENTA
IVECO Motors
SAME Diesel
PERKINS
MANUAL
SWITCH BOARDS
AUTOMATIC AT30

AUTOMATIC AT100

BURIED TANKS
EXTERNAL TANKS
      8 ÷     30
    31 ÷     60
    61 ÷   100
  101 ÷   190
  191 ÷   300
  301 ÷   400
  401 ÷   600
  601 ÷   900
  901 ÷ 1750